T8195B/Q682B,C, Y8224A
Heating or Cooling and Heating/Cooling
New Construction Thermostat,
Wallplate and Subbase
Installation Instructions for the Trained Service Technician.
Preparation
Check thermostat and subbase (if used) suitability for the
heating, cooling, or heating/cooling system. Refer to Table 1.
Assemble tools required: flat bladed screwdriver, hand or
power drill with 3/16-in. drill bit, wire cutter/stripper or
sharp knife, bubble level or plumb bob and line.
Assure power is off to the heating, cooling, or heating/
cooling system at the main fuse panel. Most buildings have
a separate switch box or circuit breaker for disconnecting
power to the heating and cooling (if applicable) equipment.
This thermostat is compatible with most heating, cooling,
or heating/cooling systems. Refer to Table 1 for thermostat
and system compatibility information.
a
If thermostat is not compatible with the system being controlled, the system will not operate. No hazard exists. The thermo-
stat will not be damaged unless it is used to directly control a line voltage system. For proper system operation, a Honeywell
R841 or R8239D1015 Isolating Relay must be added to the thermostat control circuit.
b
Consult manufacturer for installation requirements.
M3375
Recycling Notice
This control contains mercury in a sealed tube. Do not
place control in the trash at the end of its useful life.
If this control is replacing a control that contains mercury
in a sealed tube, do not place your old control in the trash.
Contact your local waste management authority for in-
structions regarding recycling and the proper disposal of this
control, or of an old control containing mercury in a sealed
tube.
If you have questions, call Honeywell Inc. at 1-800-
468-1502.
TABLE 1—THERMOSTAT AND SYSTEM COMPATIBILITY.
Type of Heating System
to be Controlled Conditions/Compatibility
Electric (Line Voltage)—typical
baseboard and radiant
The R8239D1015 Isolating Relay or R841 Silent Switching Center must be
installed in the thermostat control circuit.
a
Fan Coil Unit Compatible. Assure correct subbase identity is selected for fan control.
Gas—Direct Spark Ignition
(DSI), Intermittent Pilot (IP), and
Standing Pilot (SP)
Compatible. Assure that 24V control transformer common is accessible for
connection to thermostat cable conductor and power to the transformer is not
regularly interrupted by high temperature or limit operation.
Heat Pump Compatible. Assure correct subbase identity is selected for fan control and
changeover control (O terminal for cool and B terminal for heat). Jumper Y
to W for heat pump compressor control.
Hot Water Zone Honeywell 2-wire valves are compatible.
Some non-Honeywell 2-wire valves require an R8239D1015 Isolating Relay
in the thermostat control circuit.
a
Some 3-wire valves require an R8239A1052 Isolating Relay in the
thermostat control circuit.
a, b
Oil Assure that the 24V control transformer common is accessible for connection
to thermostat cable conductor and power to the transformer is not regularly
interrupted by high temperature, purge cycle, or limit operation.
Vent Damper Honeywell damper motors are compatible.
Some non-Honeywell damper motors require an R8239D1015 Isolating
Relay in the thermostat control circuit.
a
Check control amperage
requirement.
Warm Air Zone Most are compatible.
M3375
Vue de la page 0
1 2 3 4 5 6 7 8

Résumé du contenu

Page 1 - Wallplate and Subbase

1 69-0564—3D.F. • Rev. 11-94 • • ©Honeywell Inc. 1994 • Form Number 69-0564—3T8195B/Q682B,C, Y8224AHeating or Cooling and Heating/Cooli

Page 2 - Fig. 1—Unpack thermostat

69-0564—3 2InstallationWHEN INSTALLING THIS PRODUCT…1. Read these instructions carefully. Failure to followthem could cause a hazardous condition.2. I

Page 3 - WALLPLATE

3 69-0564—3Fig. 3—Leveling methods for wallplate orsubbase.AUTO OFFCOOLHEATONFANBOWYRGM1555SPIRIT LEVELPLUMBLINEPLUMBBOB ORWEIGHTOutlet Box Mounting (

Page 4 - Fig. 6—Thermostat mounting

69-0564—3 4Fig. 5—Methods of connecting terminals.BARRIERFOR WRAPAROUNDCONNECTION—STRIP 7/16 in. [11 mm]FOR STRAIGHTCONNECTION—STRIP 5/16 in. [8 mm]M1

Page 5 - Fig. 9—Attach cover

5 69-0564—3Fig. 8—Set timer.TIMERSETTINGKNOBTIMEINDICATORARROWM5161PROGRAM PINS (4) SEE OWNER'SMANUAL FOR DETAILSSET TEMPERATURE CONTROL LEVERSTh

Page 6 - Typical Wiring Diagrams

69-0564—3 6COOLING-ONLY SYSTEMTurn on power to the cooling equipment.Push both temperature setting levers together at least 5° F[3° C] below the room

Page 7 - 7 69-0564—3

7 69-0564—3Fig. 12—Typical hookup for T8195B Thermostat and Q682B Subbase in conventional heating/cooling system.HEATOFFCOOLONAUTOHCFANSWITCHTHERMOSTA