1 62-3047
C. H. • 12-94 • ©Honeywell Inc. 1994 • Form Number 62-3047
T104F
Thermostatic Control
The T104F Thermostatic Control is used with a V110
Valve Body to control radiators, convectors, baseboard
heating units, or other heating units with standard capacity
requirements. The control is self-powered and requires no
electrical connection. The T100A includes a setpoint dial
and valve actuator, connected by a capillary tube to a sensor.
The T104F Control attaches to the valve body by threaded
connections and may be mounted at any angle. Install the
remote sensor beneath the heating coils in the cold air re-
turn, or on a nearby wall where the air flow is not restricted.
The setpoint dial has reference marks (1-6). The control
has a low limit of 43°F (6°C) when the dial is turned fully
clockwise to the frost protection mark*. The red button
indicates the 68°F (20°C) setpoint limit. Higher settings may
be made by holding in the button while turning. The thermo-
static sensor is protected by a safety spring against tempera-
tures to 125°F (52°C).
M9730
2
3
Specifications
MATERIALS OF CONSTRUCTION:
Body: Industrial grade plastics with low thermal
conductivity.
Fastening Ring: Plated brass.
Internal Parts: Brass thermostat capsule, other metals.
TEMPERATURE RANGE: 43° to 79°F (6° to 26 °C).
MAX. SENSOR TEMPERATURE: 125°F (52°C).
MAX. OVERALL DIMENSIONS: 2-1/8 in. (54 mm) wide,
3-5/16 in. (84 mm) long. See Fig. 1.
CAPILLARY LENGTH: 6 ft. 8 in. (2 m).
TEMPERATURE SETTINGS:
These are the setpoint temperatures, which correspond
to the setpoint dial reference marks, under ideal conditions.
Factors affecting the temperature at the sensor vary for each
installation. It may be necessary to adjust the setpoint
higher or lower to obtain the desired space temperature.
Fig. 1—T104F dimensions in in. (mm).
AVAILABLE VALVE BODIES:
See Fig. 2.
Temperature 0 *123456
°F Off 43 46 54 61 68 73 79
°C Off 6 8 12 16 20 23 26
3 5/16
(84)
MAX.
2 1/8 (54)
M9731
Vue de la page 0
1 2 3 4 5 6

Résumé du contenu

Page 1 - Thermostatic Control

1 62-3047C. H. • 12-94 • ©Honeywell Inc. 1994 • Form Number 62-3047T104F Thermostatic ControlThe T104F Thermostatic Control is used with a V110V

Page 2 - Installation

62-3047 2Fig. 2—V110 Valve Bodies.OTHER AVAILABLE T100 THERMOSTATICCONTROLS (See Fig. 3):T104A Control with internal sensor.T104B Control with remote

Page 3 - ADJUSTMENT RANGE SETTING

3 62-3047Fig. 4—Typical installations.M973418 INCHMINIMUMSettings and CalibrationThe T104F Control includes an adjustable range limit-ing pin (order a

Page 4 - ACTUATOR

62-3047 4M9715ADJUSTMENTKNOBEND CAPACTUATOR232. Lift the end cap off the adjustment knob. See Fig. 6.Fig. 6—Lift the end cap off the adjustment knob.3

Page 5 - Troubleshooting

5 62-3047TroubleshootingSympton Possible Cause SolutionAll sections ofthe radiator arenot heating.1. Many radiators are over-sized and allsections are

Page 6 - 62-3047 6

62-3047 6QUALITY IS KEYHoneywell Braukmann Honeywell Braukmann Helping You Control Your WorldHoneywell Inc. Honeywell Limited—Honeywell Limitée1985 Do