INSTALLATION INSTRUCTIONS
Copyright © 1995 Honeywell Inc. • • All Rights Reserved
T874G,R Multistage Heat Pump Thermostats
and Q674F,J,L Subbases
APPLICATION
The T874G,R Thermostats with Q674F,J,L Subbases
provide 24 to 30 Vac control of a two-stage heating/one-
stage cooling heat pump system. See Table 1 for
thermostat/subbase specifications.
Table 1. Thermostat/Subbase Specifications.
Switching
Thermostat/Subbase System Fan Changeover
T874G/Q674F OFF-EM.HT.-HEAT-AUTO-COOL AUTO-ON Auto and Manual
T874G/Q674J EM.HT.-AUTO-OFF AUTO-ON Auto
T874R/Q674L EM.HT.-HEAT-OFF-COOL AUTO-ON Manual
OPERATION
On a two-heat thermostat, the two stages of heat
make
sequentially as the temperature drops.
Make
refers to the
mercury switch initiating a call for heat or cool.
There are about 2°F (1°C) between stages so that the
second stage makes only when the first stage cannot
handle the load. This is the
interstage differential
.
LEDs (light emitting diodes) are included on your subbase.
Refer to the list below for specific meaning.
The CHECK LED lights when something needs to be
checked or done to maintain efficient operation of the
system. See your heating system instructions for the
specific meaning.
The SYSTEM LED lights when the system is calling for
heating or cooling.
The AUX. HT. LED lights when the auxiliary heat (second
stage) is operating. Auxiliary heat operates when the heat
pump alone cannot handle the load.
The EM. HT. LED lights when the system switch is placed
in the EM. HT. position. Emergency heat is operating; in
most systems, the compressor has failed and the heat
pump is not operating.
LEDs are not field replaceable or addable.
RECYCLING NOTICE
This control contains mercury in a sealed tube. Do
not place the control in the trash at the end of its
useful life.
If this control is replacing a control that contains
mercury in a sealed tube, do
not
place your old
control in the trash.
Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of this control, or of an old control
containing mercury in a sealed tube.
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
69-0268-11
Vue de la page 0
1 2 3 4 5 6 ... 11 12

Résumé du contenu

Page 1 - RECYCLING NOTICE

X-XX ULINSTALLATION INSTRUCTIONSCopyright © 1995 Honeywell Inc. • • All Rights ReservedT874G,R Multistage Heat Pump Thermostatsand Q674F,

Page 2 - Wiring the Subbase

69-0268—1110T874G,R MULTISTAGE HEAT PUMP THERMOSTATS AND Q674F,J,L SUBBASESM1627ARWEXL1(HOT)L2COOLEM. HT.HEATSYSTEMSWITCHAUTOONFANSWITCH1 POWER SUPPLY

Page 3 - HT. LEDs

69-0268—1111T874G,R MULTISTAGE HEAT PUMP THERMOSTATS AND Q674F,J,L SUBBASESTHERMOSTATMOUNTING POST (2)M326650 60 70 80HEATTHERMOSTATMOUNTING

Page 4

69-0268—1112T874G,R MULTISTAGE HEAT PUMP THERMOSTATS AND Q674F,J,L SUBBASESHome and Building ControlHoneywell Limited-Honeywell Limitée35 Dynamic Driv

Page 5

69-0268—112T874G,R MULTISTAGE HEAT PUMP THERMOSTATS AND Q674F,J,L SUBBASESCAUTION1. Disconnect power supply to prevent electricalshock or equipment da

Page 6

69-0268—113T874G,R MULTISTAGE HEAT PUMP THERMOSTATS AND Q674F,J,L SUBBASESH1FALLRISECOL1 (HOT)L213C1RISE1223POWER SUPPLY. PROVIDE DISCONNECT MEANS AND

Page 7

69-0268—114T874G,R MULTISTAGE HEAT PUMP THERMOSTATS AND Q674F,J,L SUBBASESH1FALLH2FALLCORISEC1RISEL1 (HOT)L21212POWER SUPPLY. PROVIDE DISCONNECT MEANS

Page 8

69-0268—115T874G,R MULTISTAGE HEAT PUMP THERMOSTATS AND Q674F,J,L SUBBASESH2FALLH1FALLC1L1 (HOT)L21221POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERL

Page 9 - Mounting the Thermostat

69-0268—116T874G,R MULTISTAGE HEAT PUMP THERMOSTATS AND Q674F,J,L SUBBASESH2FALLH1FALLC1L1 (HOT)L21122POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERL

Page 10 - Fig. 13. Wiring connections

69-0268—117T874G,R MULTISTAGE HEAT PUMP THERMOSTATS AND Q674F,J,L SUBBASESH1FALLCL1 (HOT)L21EM. HT.LED (RED)AUX. HT.LED (GRN)W3OLGRW2EXX2BW1YAUX. HT.

Page 11 - CALIBRATION

69-0268—118T874G,R MULTISTAGE HEAT PUMP THERMOSTATS AND Q674F,J,L SUBBASESM5072A(HOT) L1 L21LACOCHPYBEOGLXW2W3RODT 1RTD 1 EHR 1RTD 2ODT 2EHR 2 RTD 3R

Page 12 - 69-0268—11

69-0268—119T874G,R MULTISTAGE HEAT PUMP THERMOSTATS AND Q674F,J,L SUBBASESFig. 10. Internal schematic and typical wiring diagram for T874R/Q674L in he