Honeywell
180850/06828,C, 18185/06828,C,L, Y8185, Y8024,
HEATING AND HEATING/COOLING
NEW CONSTRUCTION THERMOSTATS AND SUBBASES—
INSTALLATION INSTRUCTIONS
1 PREPARATION^
----------------------------------
D Check thermostat and subbase (it used) suitability
for the heating or heating/cooling system. Refer to
Tablet.
Assemble tools required: flat blade screwdriver,
hand or power drill with 3/16 in. drill bit, wire cutter/
stripper or sharp knife, bubbie level or plumb bob and
line.
LZ] If subbase or wallplate is mounted on a vertical
outlet box, order the optional 193121A Cover Plate
Assembly (inoludes cover plate, adapter ring,
screws).
and
Ensure power is off to the heating or heating/
cooling system at the main fuse panei. Most buildings
have a separate switch box or circuit breaker for dis
connecting power to the heating and cooling (if appli
cable) equipment.
THIS THERMOSTAT is compatible with virtually all heat
ing or heating/cooling systems. See Table 1 for addi
tional thermostat compatibility information.
TABLE 1—THERMOSTAT AND SYSTEM COMPATIBILITY
TYPE OF HEATING SYSTEM TO BE CONTROLLED
CONDiTIONS/COMPATIBILITY
Electric (line voltage)—typical baseboard and radiant
• The R8239D1015 Isolating Relay or R841 Silent
Switching Center must be installed in the thermostat
control circuit.^
Electric Furnace—forced air • Compatible, Ensure correct subbase identity selected
for fan control.
Gas—Direct Spark Ignition (DSl), Intermittent Pilot (IP),
and Standing Pilot (SP)
• Compatibia Ensure that the 24 V control transformer
common is accessible for connection to thermostat
cable conductor and power to transformer is not reg
ularly interrupted by high temperature or limit
operation.
Heat Pump Compatible, Ensure correct subbase identity selected
for fan control and changeover control (0 terminal for
cool and B terminal for heat),
If system with first stage heat pump and gas or oil
second stage heat, use conventional recovery
models.
If system with first stage.heat pump and electric
second stage heat, use ramp recovery model.
Hot Water Zone
Honeywell 2-wire valves are compatible.
Some non-Honeywell 2-wire valves will require a'
R8239D1015 Isolating Relay In the thermostat control
circuit.^
Some 3-wire valves will require an R8239A1052 Iso
lating Relay in the thermostat control circuib^.b
Oil
Ensure that the 24 V control transformer common is
accessible for connection to thermostat cable con
ductor and power to transformer is not regularly
interrupted by high temperature, purge cycle, or limit
operation.
If the control transformer common is not accessible,
a separate transformer and TRADELINE wallplate or
subbase with two C-C clock terminals will be
required.
Vent Damper Honeywell damper motors are compatible,
Some non-Honeyweli damper motors will require an
RS239D1015 Isolating Relay in the thermostat control
circuit.3 Check control amperage requirement.
Warm Air Zone
• Most are compatible.
Hf thermostat is not compatible with the system being controlled, the system will not operate. No hazard exists. The
thermostat will not be damaged unless it is used to directly control a line voitage system, A Honeywell R841 or
R8239D1015 Isolating Relay must be added to the thermostat control circuit for proper system operation,
^Consult manufacturer for installation requirements.
C.H.
Rev, 7-88*
Form Number 69-0258—2
®Honeywell inc. 1988
Vue de la page 0
1 2 3 4 5 6 7 8

Résumé du contenu

Page 1 - Honeywell

Honeywell180850/06828,C, 18185/06828,C,L, Y8185, Y8024, HEATING AND HEATING/COOLING NEW CONSTRUCTION THERMOSTATS AND SUBBASES— INSTALLATION INSTRUCTIO

Page 2 - 3 UNPACK THERMOSTAT

Locate thermostat about 5 ft. [1.5 m] above the floor in an area with good air circulation at average temperature. Do not mount the ther

Page 3 - 5 WIRE WALLPLATE OR SUBBASE

Fig. 3—Leveling methods for wallplate or subbase.5 WIRE WALLPLATE OR SUBBASEFollow the Instructions provided by the heating or heating/coollng

Page 4 - TYPICAL GAS VALVE

D Note the tabs on the top inside edge of the thermostat base. These fit the slots molded into the top of the wailplate or subba

Page 5 - Fig. 9—Attach cover

8 SET TIMER -----------------------------------------iZH Adjust the timer by moving the knob in clockwise direction. Do NOT reverse the knob.□ When t

Page 6 - CAUTIONS

12 CHECK OUT THERMOSTAT OPERATION'□CAUTIONSDo NOT check operation by shorting across terminais of relay or valve coil; this will

Page 7 - THERMOSTAT

AFig. 12—Hookup showing a typical heating/cooling control system.THERMOSTATAeFig. 13— Hookup showing a typical electric heating/mechanical cooling con

Page 8

Af/1\ POWER SUPPLY, PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED,/z\ CONNECT VALVE TO TERMINAL O FOR POWER ON COOLING OR TO TERMINAL