Triple Aquastat
®
Relay
J. H. • Rev. 1-95 • ©Honeywell Inc. 1995 • Form Number 60-2553—3
The L8151A is a remote bulb controller for use
with hydronic heating systems that include domes-
tic hot water service.
Provides high limit, low limit, and circulator control
for maintaining boiler temperatures.
Can provide multizone control by using a separate
thermostat and R845 Relay for each zone.
An internal transformer powers the thermostat cir-
cuit.
Shielded capillary allows convenient mounting.
Consists of a diaphragm powerhead and micro switch
assembly that responds to temperature changes in
the boiler water.
CONTENTS
Specifications ................................................. 2
Ordering Information ..................................... 2
Installation ..................................................... 2
Operation and Settings................................... 5
Checkout......................................................... 6
Vue de la page 0
1 2 3 4 5 6

Résumé du contenu

Page 1 - Triple Aquastat

1 60-2553—3L8151ATriple Aquastat® Relay J. H. • Rev. 1-95 • ©Honeywell Inc. 1995 • Form Number 60-2553—3The L8151A is a remote bulb controller f

Page 2 - Ordering Information

60-2553—3 2L8151ASPECIFICATIONS • INSTALLATION • ORDERING INFORMATIONSpecificationIMPORTANT: The specifications given in this publicationdo not incl

Page 3

3 60-2553—3L8151AINSTALLATIONIMMERSION WELL MOUNTINGNOTE: Immersion well must be ordered separately. For a listof available wells, refer to form 68-00

Page 4 - INSERT— MOUNTING CLAMP

60-2553—3 4L8151AINSTALLATIONFig. 3—Remote bulb installation.All wiring must comply with local electrical codes andordinances. The limits given in the

Page 5 - Operation and Settings

5 60-2553—3L8151AOPERATION AND SETTINGSOperation and SettingsHIGH LIMITThe high limit opens and turns off the burner when thewater temperature reaches

Page 6 - Checkout

60-2553—3 6EXAMPLE: Setpoint of 140°F (60°C) differential set at25°F (14°C). On a temperature rise, R-B breaks andR-W makes at 155°F (68°C). On a temp

Commentaires sur ces manuels

Pas de commentaire