PCR-100
PCR-110
Installation and Operating
Instructions
Electronic thermostat
EB-PCR-02 EN1H-1925GE23 R0106
Vue de la page 0
1 2 3 4 5 6 ... 15 16

Résumé du contenu

Page 1 - Instructions

PCR-100PCR-110Installation and OperatingInstructionsElectronic thermostatEB-PCR-02 EN1H-1925GE23 R0106

Page 2

7.1 Input parameters and input ranges:Parameter on display Setting range( or ) ( and or ) PresetE00 Cold store temperature difference 1 to 20 K 2 KE01

Page 3 - 2 General instructions

11☛ If the time interval between two defrost cycles is changedwhen the system is in operation, the new time interval willnot be applied until after th

Page 4 - 4 Safety

If the measured temperature is higher than the one displayed, set thepositive difference as the programming value (e.g. 2K).The temperature display is

Page 5

10 Conditions of warrantyI Warranty is provided for a period of 24 months, starting at thedate the item was delivered. Proof of this should be furnish

Page 6

14Control performance: Two-stepDisplay accuracy: ± 0.5 K internal, ±1 digit, at 25 °COperating conditions: 0 to 50 °C, 30 to 85 % R.H., excluding dewS

Page 7 - 6 Operation of the controller

15EC Declaration of Conformityas defined in the EMC Directive 89/336/EECand theEC Low Voltage Directive 73/23/EECProduct: FLICA, Electronic thermostat

Page 8

Automation and Control SolutionsHoneywell GmbHHardhofweg • 74821 Mosbach / GermanyPhone: +49 (0) 62 61 / 81-475Fax: +49 (0) 62 61 / 81-461E-Mail: Cool

Page 9 - 7 Programming

2TABLE OF CONTENTS11 Unpacking the unit and conditions of use312 General instructions 313 Use and function 33.1 Use for the purpose intended 33.2 Func

Page 10 - ( or ) ( and or ) Preset

1 Unpacking the unit and conditions of useBefore and when unpacking the unit, make a visual inspection toidentify any possible damage which may have o

Page 11

If the unit is used for purposes other than those stated here, it shall not be considered to be use for the purpose intended.I Only connect sensors su

Page 12 - 9 Appendix

I If the unit cannot be operated without the risk of danger, it mustbe taken out of service and precautions taken so that it cannot beswitched on agai

Page 13 - 11 Technical data

I Snap – in housings: Fit the unit in an aperture 28,5 x 70,5 mm and secure it with therelevant mounting frame.a) housings with terminal box coverplat

Page 14

☛ Instructions:I For PCR-110 the total current via terminal 5 of the common relayconnection must not exceed 10 A.I Pay attention to the contact loadin

Page 15 - EC Declaration of Conformity

86.1 Switching on the operating voltageThe controller is started by means of a control switch provided by thecustomer.The first time the controller is

Page 16

9I Input values are always changed using the or key with the key held down.I Input parameters, e.g. the switching difference is shown as “E”with a