4/00 UDC 3300 Controller Product Manual 163
5.8 Setpoint Ramp Rate
Configuration
You can configure a Setpoint Ramp Rate that will apply to any Local
setpoint change immediately.
Refer to the Configuration Section to enable the ramp for either loop and
set an upscale or downscale rate value.
Make sure SP RAMP and SP PROG are disabled.
Operation
When a local setpoint change is made, the controller will ramp from the
original setpoint to the new one at the rate specified. This changing
(current) setpoint can be viewed as SPn on the lower display.
Press the LOWER DISPLAY key until you see SPn and the setpoint
value in the lower display.