1 60-1165—6
Q674 Switch Positions
Model System Fan
A Heat-Auto-Cool Auto-On
B Heat-Off-Cool Auto-On
C Off-Auto Auto-On
D None None
E Off-Heat-Auto-Cool Auto-On
G Off-Auto None
T874A-F Multistage
Thermostats/Q674A-E,G Subbases
TRADELINE
®
Installation Instructions for the Trained Service Technician.
Operation
On a 2-heat thermostat, the two stages of heat make
sequentially as the temperature drops. Make refers to the
mercury switch initiating a call for heat or cool.
There are about 2° F [1° C] between stages so that the
second stage makes only when the first stage cannot handle
the load. This is the interstage differential.
M3375
Recycling Notice
This control contains mercury in a sealed tube. Do not
place control in the trash at the end of its useful life.
If this control is replacing a control that contains mer-
cury in a sealed tube, do not place your old control in the
trash.
Contact your local waste management authority for
instructions regarding recycling and the proper disposal of
this control, or of an old control containing mercury in a
sealed tube.
Installation
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condi-
tion.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service tech-
nician.
4. After installation is complete, check out product
operation as provided in these instructions.
CAUTION
1. Disconnect power supply to prevent electrical
shock or equipment damage.
2. To prevent interference with the thermostat
linkage, keep wire length to a minimum and
run wires close as possible to the subbase.
3. Do not overtighten thermostat captive mount-
ing screws because damage to subbase threads
can result.
4. Do not short across coil terminals on heating
relay or gas control. This can burn out the
thermostat heat anticipator.
IMPORTANT: Thermostats are calibrated at the factory
by using subbases mounted at true level. Inaccurate
subbase leveling will cause thermostat control de-
viation.
LOCATION
Locate the subbase about 5 ft [1.5m] above the floor in
an area with good air circulation at average temperature.
Do not mount the subbase where the thermostat may be
affected by:
drafts or dead spots behind doors and in corners.
hot or cold air from ducts.
radiant heat from sun, appliances or fireplace.
concealed pipes and chimneys.
unheated (uncooled) areas such as an outside wall
behind the thermostat.
MOUNTING THE SUBBASE
The thermostat subbase can be mounted on a vertical
outlet box, horizontal outlet box or directly on the wall.
1. If you must mount the subbase on a vertical outlet
box, order Honeywell 193121A Adapter Assembly (Fig. 1).
The assembly includes an adapter ring, two screws and a
cover plate to cover marks on the wall. Install the ring and
cover plate on the vertical outlet box.
J.H. • Rev. 5-94 • • ©Honeywell Inc. 1994 • Form Number 60-1165—6
Application
The T874A-F Thermostats provide 24 to 30 Vac control
for heating and/or cooling systems as listed in Table 1.
TABLE 1—THERMOSTAT HEATING AND/OR
COOLING STAGES.
The Q674A-E,G Subbases provide wiring terminals,
system and fan switching, and mounting bases for T874
Thermostats as listed in Table 2.
TABLE 2—SUBBASE SWITCHING POSITIONS.
T874 A B C D E F
Heating Stages 1 122—2
Cooling Stages 1 2122—
M3375
Vue de la page 0
1 2 3 4 5 6 ... 11 12

Résumé du contenu

Page 1 - T874A-F Multistage

1 60-1165—6Q674 Switch PositionsModel System FanA Heat-Auto-Cool Auto-OnB Heat-Off-Cool Auto-OnC Off-Auto Auto-OnD None NoneE Off-Heat-Auto-Cool Auto-

Page 2 - Fig. 4—Wiring connections

1060-1165—62. Move the system switch to AUTO or HEAT (ifused).3. After one minute, read the ammeter and record thereading:Stage 1: __________ amperes.

Page 3

11 60-1165—6CalibrationTHERMOSTATT874 Thermostats are accurately calibrated at the factory.They do not have provision for field calibration.THERMOMETE

Page 4

1260-1165—6www.honeywell.com/yourhomeAutomation and Control SolutionsHoneywell International Inc. Honeywell Limited—Honeywell Limitée1985 Douglas Driv

Page 5 - 5 60-1165—6

260-1165—6Fig. 1—Installation of subbase on outlet box.2. Pull electrical wires through the cover plate (ifused) and subbase cable opening (Fig. 3). S

Page 6

3 60-1165—63. Firmly tighten each terminal screw.4. Fit wires as close as possible to the subbase. Pushexcess wire back into the hole.5. Plug hole wit

Page 7 - 7 60-1165—6

460-1165—6Fig. 8—T874A-D/Q674A in standard heating/cooling system.Fig. 9—T874C,D/Q674B in standard heating/cooling system with separate transformers f

Page 8 - LEVER STOP BRACKETS

5 60-1165—6Fig. 10—T874D/Q674B in standard heating/cooling system with single transformer for heating andcooling. Exact replacement for York model no.

Page 9 - Settings

660-1165—6Fig. 12—T874A,D,F/Q674D in standard heating/cooling system.Fig. 13—T874D/Q674E in standard heating/cooling system.

Page 10 - Checkout

7 60-1165—6Fig. 14—T874A-F/Q674G in standard heating/cooling system.Fig. 15—T874C/Q674B in standard application.

Page 11 - Calibration

860-1165—6Fig. 16—Typical Q674 terminal designations. The thermostat and subbase used determines the numberof system components controlled.TEMPERATURE

Page 12 - 60-1165—6

9 60-1165—69. Firmly tighten the mounting screw.10. If the HEAT and COOL levers are to be locked inplace at a specific temperature, use the two insula