Honeywell TB7600 Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Thermostats Honeywell TB7600. Honeywell TB7600 User's Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 24
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
REFERENCE MANUAL
Put Bar Code Here
63-4523-01
BACnet Integration Manual for
TB7600 Series Thermostats
Contents
Product Overview ............................................................. 1
Compatibility ..................................................................... 2
Tips and Things You Need to Know .................................. 2
Wiring guidelines .............................................................. 3
Network Configuration ...................................................... 4
Network Adapter ............................................................... 6
Integration ......................................................................... 7
Troubleshooting ................................................................11
Appendix ...........................................................................12
TB7600 Series Protocol Implementation
Conformance Statement (PICS) ..................................12
BACnet Objects Supported ...............................................13
PRODUCT OVERVIEW
The TB7600 PI thermostat family is specifically designed for
single stage and multi-stage control of heating/cooling
equipment such as rooftop and self-contained units. The
TB7600 Series are communicating thermostats with models
available in BACnet
®
MS/TP and ZigBee
®
wireless mesh
protocols and can be easily integrated into a WEBs-AX
building automation system based on the NiagaraAX
®
platform.The product features an intuitive, menu-driven, back-
lit LCD display, which walks users through the programming
steps, making the process extremely simple. Accurate
temperature control is achieved due to the product’s PI time
proportional control algorithm, which virtually eliminates
temperature offset associated with traditional, differential-
based thermostats.
TB7600 Series
Thermostat
TB7600 Series
Thermostat with
Occupancy Sensor
The TB7600 thermostats are also compatible with the
Honeywell PIR occupancy sensor covers. Thermostats
equipped with a PIR cover provide advanced active
occupancy logic, which will automatically switch occupancy
levels from Occupied to Unoccupied as required by local
activity being present or not. This advanced occupancy
functionality provides advantageous energy savings during
occupied hours without sacrificing occupant comfort. All
thermostats can be ordered with or without a factory installed
PIR cover.
More Information
The additional following documentation is available on http://
customer.honeywell.com:
TB7600 Series Installation Instructions (form number 62-
2016).
TB7600 Series with Humidity Control Installation
Instructions (form number 62-2017).
The PIR Application Guide for TB7600 Series (form
number 63-4525).
Vue de la page 0
1 2 3 4 5 6 ... 23 24

Résumé du contenu

Page 1 - TB7600 Series Thermostats

REFERENCE MANUALPut Bar Code Here63-4523-01BACnet Integration Manual for TB7600 Series Thermostats ContentsProduct Overview ...

Page 2 - COMPATIBILITY

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS63-4523—01 10Free programmed object or loopsAs for the application program, you might want to r

Page 3 - WIRING GUIDELINES

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS11 63-4523—01TROUBLESHOOTING Error / Trouble ConditionPossible Cause SolutionThermostat does no

Page 4 - NETWORK CONFIGURATION

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS63-4523—01 12APPENDIX A: BACNET OBJECTSTB7600 SERIES PROTOCOL IMPLEMENTATION CONFORMANCE STATEM

Page 5 - EIA-485 Repeaters

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS13 63-4523—01BACNET OBJECTS SUPPORTEDDevice ObjectsTable 4. Device ObjectsObject NameType and I

Page 6 - NETWORK ADAPTER

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS63-4523—01 14Objects Table Table 5. ObjectsObject NameType and InstanceObject PropertyTB7600A5x

Page 7 - INTEGRATION

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS15 63-4523—01Unoccupied Heat SetpointAV 44 Present_Value (R,W) √√√√√√√√√√Unoccupied Cool Setpoi

Page 8 - 63-4523—01 8

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS63-4523—01 16Economizer Changeover SetpointAV 77 Present_Value (R,W) √√Economizer Minimum Posit

Page 9 - Graphical interfaces

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS17 63-4523—01Standard Object Types SupportedTable 6. Standard Object Types Supported a The fo

Page 10 - Retries and Timeouts

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS63-4523—01 18Property Value Range Restrictions for AI and AV objectsTable 8. Property Value Ran

Page 11 - TROUBLESHOOTING

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS19 63-4523—01List of Property Enumeration Sets for BI and BV objectsTable 9. List of Property E

Page 12 - STATEMENT (PICS)

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS63-4523—01 2COMPATIBILITYHoneywell TB7600 Series thermostat compatiblity information is provide

Page 13 - BACNET OBJECTS SUPPORTED

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS63-4523—01 20Property Enumeration Sets for MV ObjectsTable 10. Property Enumeration Sets for MV

Page 14 - Objects Table

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS21 63-4523—01Temporary Occupancy TimeMV611 0 hour3 hours2 1 hour3 2 hours4 3 hours5 4 hours6 5

Page 15 - Table 5. Objects

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS63-4523—01 22Heating Stages MV731 1 Stage2 Stages2 2 StagesCooling Stages MV741 1 Stage2 Stages

Page 16

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS23 63-4523—01

Page 17 - Proprietary Properties

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATSAutomation and Control SolutionsHoneywell International Inc.1985 Douglas Drive NorthGolden Vall

Page 18 - 63-4523—01 18

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS3 63-4523—01WIRING GUIDELINES Overview Honeywell uses EIA-485 as the physical layer between the

Page 19 - 19 63-4523—01

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS63-4523—01 4NETWORK CONFIGURATION EIA-485 networks use a daisy chain configuration. A daisy ch

Page 20 - 63-4523—01 20

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS5 63-4523—01Maximum Cable Length The maximum length of a chain is related to its transmission s

Page 21 - 21 63-4523—01

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS63-4523—01 6End Of Line (EOL) ResistorsMS/TP network must be properly terminated. For daisy cha

Page 22 - 63-4523—01 22

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS7 63-4523—01Network Adapter Status LEDTable 3 shows the different possibilities with the Status

Page 23 - 23 63-4523—01

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS63-4523—01 8Typical Graphical User Interface (GUI) Objects The following objects should be typi

Page 24 - Printed in U.S.A

BACNET INTEGRATION MANUAL FOR TB7600 SERIES THERMOSTATS9 63-4523—01Recommended Configuration ObjectsThe following objects and group objects should be

Commentaires sur ces manuels