BACnet/IP MODULE
Analog Input
The Analog Input object type defines a standardized object whose
properties represent the externally visible characteristics of an analog
input, such as a gas sensor.
Supported properties for the Analog Input object type are :
Object_Identifier, Object_Name, Object_Type, Status_Flags,
Event_State, Reliability, Present_Value, Out_of_Service and Units.
Analog Value
The Analog Value object type defines a standardized object whose
properties represent the externally visible characteristics of an analog
value. An "analog value" is a control system parameter residing in the
memory of the BACnet Device, such as a gas alarm level.
Supported properties for the Analog Value object type are :
Object_Identifier, Object_Name, Object_Type, Status_Flags,
Event_State, Reliability, Present_Value and Units.
Binary Input
The Binary Input object type defines a standardized object whose
properties represent the externally visible characteristics of a binary
input. A "binary input" is a physical device or hardware input that can be
in only one of two distinct states, such as the 301ADI digital inputs.
Supported properties for the Binary Input object type are :
Object_Identifier, Object_Name, Object_Type, Status_Flags,
Event_State, Reliability, Present_Value, Polarity, Inactive_Text and
Active_Text and Out_of_Service.