L7224U OIL AND ELECTRIC BOILER ELECTRONIC AQUASTAT
®
CONTROLLER
69-1720EFS—07 6
220, followed by °F or °C. Pressing the I button again will
display the LL (Low Limit) followed by a three-digit
number and the corresponding degree designator. See
Table 3 for explanation of display readout.
After approximately 60 seconds without any key presses,
the display will enter a dim display mode. To return to the
bright display mode, simply press and release any key.
1
Display shows local setting; not the setting as modified by an
external enviracom control.
2
Settings are viewable only if the outdoor reset module and out-
door temperature sensor are installed and functioning properly.
3
Settings are viewable only if the domestic hot water module
and sensor are installed and functioning properly.
Operation
The L7224U can be in any of four operational states:
Normal, High Limit, Low Limit and Error. The controller
moves back and forth from High Limit to Normal to Low
Limit state as part of normal operation. The operating
states are:
1. Normal: Boiler temperature went below the High
Limit setting (minus the Differential) and has not
exceeded the High Limit setting; or, the boiler tem-
perature went above the Low Limit setting and has
not gone below the Low Limit setting (minus the Dif-
ferential).
2. High Limit: Boiler temperature went above the High
Limit setting and has not dropped below the High
Limit setting (minus the Differential).
3. Low Limit: Boiler temperature went below the Low
Limit setting (minus the Low Limit Differential) and
has not gone above the Low Limit setting.
4. Error: The controller has detected an error condition
(e.g., open sensor) and has shut down the burner
output. The Zone Control (ZC) output is energized.
The controller continues to monitor the system and
automatically restarts if the error condition clears.
Refer to Table 6–8.
The operating sequence for the L7224U is shown in Table
5.
High Limit Controller
The High Limit opens and turns off the burner when the
water temperature reaches the setpoint. The High Limit
automatically resets after the water temperature drops
past the setpoint and through the adjustable Differential.
Low Limit and Circulator Controller
On a temperature rise, the burner circuit breaks and the
circulator circuit makes (assuming no call for heat is
present) at the Low Limit setpoint. On a temperature drop
of 10 °F (6 °C) below the Low Limit setpoint (with the
adjustable Differential at the minimum setting of 10 °F
(6 °C)), the burner circuit makes and the circulator circuit
breaks. Refer to Fig. 7.
Fig. 7. Setpoints and differentials.
Table 3. Display readout definitions.
Text Description Display
Err Error Code (if one is present)

bT Boiler Temperature

HL
High Limit
1

HdF High limit differential

LL Low Limit set-point (L7224 only)

Ldf Low Limit differential (L7224 only)

tt Local Thermostat Status

ttE EnviraCOM Thermostat Status

brn B1 (Burner) output (ON or OFF)

Cir C1 (Circulator) output (ON or OFF)

ZC ZC (Zone Control) output (ON or OFF)

Zr ZR (Zone Request) Call for HEAT (ON or OFF)

duu ZR Configured as Domestic Hot Water
Request (L7224, L7248L only)

ASC Anti Short-Cycle Timeout

bSP
Boiler Set-Point
2

dhc
DHW Module Connected
3
(YES or NO)

ot
Outdoor Temperature
2

otL
Outdoor Temperature Low
2

otH
Outdoor Temperature High
2

btL
Boiler Temperature Low
2

bP
Boost Period
2

bS
Boost Step
2

UUS
Warm Weather Shutdown Temperature
2

LOW LIMIT
SETTING
HIGH LIMIT
SETTING
SWITCH BREAKS ON
TEMPERATURE RISE.
BURNER TURNS OFF.
CIRCULATOR OPERATES
ON A CALL FOR HEAT.
SWITCH MAKES ON
TEMPERATURE FALL.
BURNER OPERATES ON A
CALL FOR HEAT.
WITH NO HEATING
DEMAND, SWITCH BREAKS
ON TEMPERATURE RISE.
SWITCH MAKES ON
TEMPERATURE FALL,
BURNER IS ON TO
MAINTAIN MINIMUM
WATER TEMPERATURE.
CIRCULATOR IS OFF.
M23365
WHEN WATER REACHES LOW LIMIT SETTING, THE BURNER SHUTS
OFF OR THE CIRCULATOR PUMP STARTS (WHEN CALLING FOR HEAT).
1
1
10ºF (6ºC)
DIFFERENCE
10ºF (6ºC)
DIFFERENCE