L7224U OIL AND ELECTRIC BOILER ELECTRONIC AQUASTAT
®
CONTROLLER
9 69-1720EFS—07
Table 5. L7224/L7248 Controller Operating Sequence.
* Error condition only available when the Outdoor Reset
Module is installed.
Action System Response
Thermostat
calls for heat.
Circulator starts when water temperature is
above Low Limit setting (if applicable) or above
the Thermal Purge Temperature Limit (tPL) if
Thermal Purge is enabled. Boiler temperature
is checked. Burner starts when water
temperature is below High Limit setting minus
the differential or at or below the Thermal
Purge Temperature Limit (tPL) for cold start
boilers if the Thermal Purge Temperature Limit
is enabled. If tPL is enabled, the burner may
also start if the boiler temperature is cooling at
10 ºF or greater per minute or the Thermal
Purge Time Delay (tPt) has expired.
If Anti Short-Cycle Time is enabled, the burner
does not start until the set Anti Short-Cycle
Time between cycles expires after the previous
call for heat was satisfied.
Boiler
temperature
exceeds the
High Limit.
Burner is turned off. Burner restarts when the
water temperature drops below the High Limit
setting minus the Differential. If Thermal Purge
is enabled, the burner is turned on when either
the Thermal Purge Temperature Limit is
reached, the Thermal Purge Time Delay has
expired or the boiler temperature cooling rate
exceeds 10 ºF/minute.
Thermostat is
satisfied.
Circulator and burner turn off.
Boiler
temperature
drops below
the Low Limit
setting minus
the differential
(if applicable).
Burner is turned on, Circulator is turned off.
Burner stops when the water temperature
exceeds the Low Limit setting. Power to Zc is
removed.
Error
conditions
1-5.
If an error condition is detected, all outputs
except ZC are shut down. Burner is off. The
controller continues to function and restarts
when error is corrected.
During the error check sequence, the system
checks for drift in the sensor and corrosion in
the connections.
Error
condition 6.
EnviraCOM communication is not available.
Error
condition 7.
The controller has reset the High Limit, Low
Limit and Differential Setting to a default setting
and will continue to run at those settings.
Performance of the system will be degraded.
Error
condition 8.
If the error condition is detected, all outputs
except ZC are shut down. Burner is off.The
controller continues to function and restarts
when all three user keys have been pressed
longer than 60 seconds.
Error
condition 9*.
System continues to run with no outdoor reset
functionality
Error
condition
10*.
System continues to run with outdoor reset
parameters enabled as programmed. Error
cleared automatically.
Error
condition 11*.
System continues to run with boiler temp set to
High Limit.
Table 6. L7224 Controller Operating Sequence with mul-
tiple zones connected through the ZR terminal
Action System Response
Zone Request (ZR)
terminal is connected
to L1 (Zone calls for
heat).
Boiler temperature is checked. Burner
starts when water temperature is below
High Limit setting or at or below the
Thermal Purge Temperature Limit (tPL) for
cold start boilers if the Thermal Purge
Temperature Limit is enabled. If tPL is
enabled, the burner may also start if the
boiler temperature is cooling at 10 ºF or
greater per minute or the Thermal Purge
Time Delay (tPt) has expired. Anti Short-
Cycle Time is applied, see Table 5.
Boiler temperature
exceeds the High
Limit.
Burner is turned off. Burner restarts when
the water temperature drops below the
High Limit setting minus the Differential. If
Thermal Purge is enabled, the burner is
turned on when either the Thermal Purge
Temperature Limit is reached, the Thermal
Purge Time Delay has expired or the boiler
temperature cooling rate exceeds 10 ºF/
minute.
Zone Request input is
de-energized (Zones
are satisfied).
Burner turns off.
Boiler temperature
drops below the Low
Limit setting minus
the differential (if
applicable).
Burner turns on and Zone Control is de-
energized. Burner turns off and Zone
Control is re-energized when the water
temperature exceeds the Low Limit setting.
Table 7. Controller Operating Sequence with External
Low Limit device connected trough the ZR terminal.
Action System Response
Zone Request (ZR)
terminal is connected
to L1 (External Low
Limit call for heat).
Boiler temperature is checked. Burner
starts when water temperature is below
High Limit setting. Circulator turns off.
Boiler temperature
exceeds the High
Limit.
Burner is turned off. Burner restarts
when the water temperature drops
below the High Limit setting minus the
Differential.
Zone Request input is
de-energized (External
Low Limit is satisfied).
Burner is turned off.
Table 8. L7224 Controller Operating Sequence with
Domestic Hot Water connected trough the ZR terminal.
Action System Response
Zone Request (ZR) terminal
is connected to L1
(Domestic Hot Water calls
for heat).
Boiler temperature is checked. Burner
starts when water temperature is
below High Limit setting.
Boiler temperature exceeds
the High Limit.
Burner is turned off. Burner restarts
when the water temperature drops
below the High Limit setting minus
the Differential.
Zone Request input is de-
energized (Domestic Hot
Water is satisfied).
Burner is turned off.