L7224U OIL AND ELECTRIC BOILER ELECTRONIC AQUASTAT
®
CONTROLLER
7 69-1720EFS—07
NOTE: Setting the Low Limit above the High Limit
less the High Limit Differential is not allowed
as improper circulator and Zone Control
functions could result.
Anti Short-Cycle Feature
The Anti Short-Cycle feature allows for field selection of a
minimum delay time between burner cycles. Should a call
for heat occur following the end of the previous heat cycle
and before the Anti-Short Cycle delay time is expired, the
circulator will be allowed to run, but the burner will be held
off until the time has elapsed.
NOTE: The Anti Short-Cycle feature is blocked if
DHW demand occurs. DHW demands are ser-
viced immediately, without any delay.
NOTE: When the Aquastat is connected to the oil
primary and/or thermostat via the EnviraCOM
bus, the Anti Short-Cycle time does not apply
to recycle events such as loss of airflow or
flame. It applies only to loss of demand.
ZR-Domestic Hot Water (DHW)
Request
The ZR terminal on the L7224U can be selected to
service an indirect water heater heat request. This
parameter is set via the 3 digit display (see “Adjusting
Settings” on page 5). A heat request via the ZC terminal
will have priority over all other features such as the Anti-
Short Cycle feature or those enabled by the Outdoor
Reset Module (See form 69-2235 for more information).
Frost Protection
The Frost Protection function protects the boiler and
potentially the boiler plumbing from possible damage
which may occur should the water in the system begin to
freeze. The Frost Protection feature is enabled only in the
L7248 (cold start models). The feature default setting is
enabled (ON), but can be disabled using the 3-digit
display. See “Adjusting Settings” on page 5.
When the Boiler temperature drops to the Frost Protection
Limit temperature (fixed 40 °F), the burner is forced on.
The Circulator and ZC outputs remain in the same state
as before the Frost Protection function was enabled.
They can be either ON or OFF during the Frost Protection
cycle.
When the Boiler temperature reaches the Frost Protection
Limit temperature plus a fixed 10 ° F differential, the
burner is turned off unless requested to stay on due to a
different demand.
Thermal Purge Operation
The intent of thermal purge is to insure usable residual
heat in the boiler is circulated until it is sufficiently
depleted from the system before the burner is allowed to
fire. To that end, on a call for heat, the burner is held off
while the circulator runs until the boiler temperature drops
to the thermal purge temperature or a time delay is
exceeded. Both of these parameters are adjustable.
When the boiler temperature reaches the thermal purge
temperature, the burner is allowed to fire. Thermal purge
is only applied when the low limit is set to OFF and will not
interfere with a domestic hot water call for heat or boilers
equipped with Honeywell outdoor reset accessories. For
applications where a Low Limit must be set, thermal
purge is not applied.
In addition to the thermal purge temperature and thermal
purge time delay parameters, two other conditions release
the Aquastat from thermal purge in order to maintain
comfort in the space:
The boiler temperature has dropped 10 °F from the
beginning of the thermal purge.
Boiler temperature is cooling at a rate greater than
5 °F/minute while the circulator is running.
The thermal purge feature applies to single zone as well
as multi-zone applications.
Thermal Purge Settings
Some thermal purge parameters are configurable using
the 3 digit display. See “Adjusting Settings” on page 5.
Thermal purge may be disabled by setting the thermal
purge temperature limit to "OFF".
Thermal Purge and Domestic Hot
Water
The thermal purge feature is automatically disabled
whenever there is a call for domestic hot water from the Zr
terminal to ensure hot water is available in a timely
manner. See “ZR-Domestic Hot Water (DHW) Request”
on page 7.
Pump Cycling
The Pump Cycling feature exercises the system pump for
15 seconds after a non-adjustable five day period of no
boiler activity. The Pump Cycling feature default setting is
enabled (ON) but can be disabled (OFF) using the 3-digit
display. See “Adjusting Settings” on page 5.
CHECKOUT
Put the system into operation and observe at least one
complete cycle to make sure that the controller operates
properly. See TROUBLESHOOTING section to use LED
to assist in determining system operation.
Table 4. Thermal Purge Settings.
Parameter name Minimum value Maximum Value Default
Boiler temperature drop Not adjustable Not adjustable 10 °F
Thermal purge temperature limit 120 °F (or OFF) 160 °F 140 °F (L7248)
Thermal purge temperature rate of drop Not adjustable Not adjustable 5 °F/minute
Thermal purge time delay 1 minute 10 minutes 2 minutes